Power Control Centre / Motor Control Centre
SALIENT FEATURE 1. ELECTRICAL SUPPLY CHARACTERISTICS Normal Voltage
: 415 Volts, 3 Phase, 4 Wire, 50 Hz, AC : Voltage Plus/Minus 6%
Frequency - Plus/minus 3% combined - Plus/Minus 6% 2. STANDARDS All
materials, equipment and accessories used in the manufacture shall
confirm to relevant Indian/British/IEC 3. CONSTRUCTIONS a) 14/16
SWG. CRCA sheet steel cubicle type Indoor/Outdoor floor mounting
free standing / wall mounting. b) Totally enclosed dust damp and
vermin proof. c) Non deteriorating synthetics rubber gasket shall
be used between all adjacent units and beneath all covers and door.
d) Vents and other opening shall be provided with non-rusting
screens for vermin proofing. e) MCC/PCC shall be same height, width
and depth as well as bolted together to form a continuous flush
switch board, suitable for front board, suitable for front board,
operation. f) The MCC/PCC shall be fabricated from structural steel
section and sheet steel. The base channel shall be of 3mm thick and
75mm wide body sheet steel shall have 1.5/2 mm thickness. The
design and construction shall be rigid and robust, welded
construction will be provided. All steel works shall be flawless
and have smooth finish. g) Adequate lifting facilities shall be
provided on each section of MCC lifting eyes may be
removable/foldable. h) Inside surface shall be painted with
anti-condensation paint. All feeder compartment shall be provided
with doors, doors shall be hinged type with quick release fasteners
and lift off type hing. Doors opening shall be restricted, by
suitable means to avoid damage to door mounted equipment. i)
Separate compartments shall be provided for MCC incoming and
outgoing feeders, bus bar , cable boxes, which will be fully and
effectively segregated from one other, so that fault in any one
compartment shall not cause damage to equipment in any other
compartment. j) ISOLATOR COMPARTMENT Isolator to be interlocked
with door to prevent opening or closing of the door in the closed
(ON) position of the Isolator , in case of compartment type of
feeders, provision for padlocking the isolator in open position
also could be made on request. k) BUS BAR COMPARTMENT TPN Bus bar
of the rating as specified shall be provided in separated
compartment, such compartment in each panel shall have front
removal cover properly fixed with suitable number of screws. l)
CABLE BOX COMPARTMENT The outgoing feeders shall be wired upto
terminal box, with shall be mounted in separate compartment at top.
All covers to this compartment shall also be removable type.
Considering size and number of cables to be connected bus bars
shall provided in cable box. 4. EQUIPMENT/COMPONENTS: A) BUS BARS
1) Bus bar shall be of uniform cross section of electrolytic
quality aluminum rated as per current rating .Busbar shall be air
insulated, enclosed, having barriers /covers. Caution live busbars
name plate shall be on barriers/covers. B) FEEDER ARRANGEMENTS 1)
Each feeder shall be provided with barriers on all sides such that
compartmentalization is possible. 2) Compartment size shall be
integral multiples of one or two basic size. 3) The control
components except those coming on doors shall be mounted on a
common base plate ,fixed with the frame of the vertical section. 4)
Each feeder designation as per single line diagram .The labela‚¬?s
shall be black of Perspex acrylic unbreakable sheets with 20mm size
letters engraved in white. C) ISOLATOR 1) Isolators shall be two
position (ON/OFF) type, heavy duty ,load break ,quick make and
quick break type and suitable for front of board operation. 2)
Isolator for motor feeders shall be motor duty type i.e. capable to
interrupting the locked rotor current of motors. 3) All live
terminals on the isolators to be adequately/shrouded to prevent
accidental contact and danger to the personnel. D) WIRINGS 1) All
control wiring shall be carried out through common wire ways. These
shall not cross the bus bar chamber. All control wiring shall be
easily accessible for maintenance. 2) Power wiring shall be carried
out with PVS insulated standard copper/ Aluminum Conductors of 650
V grade having adequate current carrying capacity. 3) Necessary
colour codes shall be adopted for power and control wiring for easy
identification. 4) Control wiring shall be single core/ multicore
,PVC insulated copper conductor of size 2.5 mm cross section and
with 650V grade flame resisting insulation. 5) Circuit involving
current transformers shall have 1100V grade cable. 6) Each control
wire shall be identified at both ends with wire designations by
means of unbreakable ferrules, in accordance with IS:375. 7)
Control wiring where ever terminated shall be in single layer,
formation. Double layer wiring shall not be adopted ,not more than
two wires shall be connected to one terminal. 8) Connection from
vertical bus bars to the feeders switches shall withstand short
circuit level specified, in case fuses are provided on the incomer,
these connections shall be desi